Product Details
Pre programmed tests, simple operation and can be upgraded to a downloading tester.
A new innovation in PAT testers, the Gamma PAT is a handheld, battery operated PAT tester and is suitable for all contractors, schools and general purpose use.
With a built-in calibration checkbox, and the option to upgrade it to a downloading tester in the future, the Gamma PAT stands out in a league of its own. The design of the LCD display also incorporates a red and green LED, giving a clear colour indication for Pass or Fail, as well as displaying the results and information on the LCD.
Diagrams on the display indicate the required connections for each test, helping to eliminate some of the common mistakes made when PAT testing. There are also user settable pass thresholds in order to eliminate incorrect fail indications on appliances with long leads.
Carrying out IT equipment tests with the Metrel Gamma PAT
The Gamma PAT portable appliance tester has a list of pre-programmed test processes built in, to test IT equipment you simply need to select the relevant test process from the list and the tester will do the rest. This tester also features a 250V insulation test, which enables you to test any surge protected devices.
Key Features of the Metrel Gamma PAT Lite
Earth Bond, Insulation & Earth Leakage Tests
Option to upgrade to a downloading tester
Can be connected to a barcode scanner
Built-in battery charger
The Gamma PAT Lite portable appliance tester comes supplied with:
6 x AA NiMH batteries
Mains charging adaptor
IEC cable for extension lead testing
Test probe with crocodile clip
Manufacturers calibration certificate
Instruction manual
Soft carry case
1000 PASS Labels
500 FAIL Labels
3 year warranty
Specfication
Earth Bond Test (IT Safe)
Test Current: 200mA DC
Range: 0 - 19.99Ω
Resolution: 0.01Ω
Default Pass Value: 0.2Ω
Insulation Resistance
Test Voltage:
500V: >500V DC at 1mA
250V: >250V DC at 1mA
Default Pass Value: Class I - 1MΩ, Class II - 2MΩ
IEC & Extension Lead Test
Earth Continuity: 200mA DC
Insulation Test: 500V DC
Wiring Test: Live, Neutral Continuity& Polarity
Earth Bond Default Pass Value: 0.2Ω
Insulation Resistance Default Pass Value: 1MΩ
Substitute Leakage Test - Class I
Test Voltage: 40V AC Nominal
Display Range: 0.10mA - 19.99mA
Pass Value: 0.75mA
Substitute Leakage Test - Class II
Test Voltage: 40V AC Nominal
Display Range: 0.10mA - 19.99mA
Pass Value: 0.25mA
Power Socket Test
Input Voltage Range: 230V +10%, -15% AC
Indicators: Phase to Earth Voltage, Phase to Neutral Voltage, Neutral to Earth