Megger MFT1741+ (Plus Version) Multifunction Tester

Megger
  • Can test Electric Vehicle Charge Points (when used in conjunction with the Megger EVCA210 adaptor*)
  • “Confidence meter” measurement analysis (patent pending)
  • 18th Edition compliant
  • Ambidextrous operation
  • Manufacturer CAL cert in the box
Special Price £1,344.00 £1,120.00 Regular Price £2,398.80

Availability: In stock

Product Code
MEGMFT1741PLUS

Key Features:

  • Testing of Electric Vehicle Charge Points (when used in conjunction with an EV charge point adaptor such as the Megger EVCA210*)
  • Enhanced non-trip loop impedance measurement technology
  • “Confidence meter” measurement analysis (patent pending)
  • Full single and 3 phase compliant installation testing
  • 10 mA to 1 A single and 3 phase RCD testing
  • Earth testing and stake-less testing for electrode resistance measurement*
  • Simple colour-coded test selection
  • Ambidextrous operation
  • Internal memory and Bluetooth® communications
  • EN61010 CAT IV safety rating and tough IP54 case

Particularly effective in areas that suffer from high electrical noise, this instrument provides all the tests needed to complete the necessary electrical certifications for industrial, commercial and domestic fixed wiring installations.

Save time and get non-trip loop testing down to 8 seconds with the MFT1741+’s new Loop Impedance testing technology! This innovative ability also increases the accuracy of results as it prevents the RCD from influencing the total loop impedance value. What’s more, you can measure the degree of confidence in the accuracy of the measured loop impedance, thanks to Megger’s new Confidence Meter measurement analysis (patent pending). This technology uses the digital ARC to indicate the analytical process, then continually monitors and adjusts the measurement when circuit noise is present, resulting in a dramatically improved and repeatable test result.

You can even test electric vehicle charge points with the MFT1741+! It comes with an automatic EV Charge Point RCD test sequence, including the 6 mA DC test*.

Easy-to-use and quick to learn, this instrument has no hidden menus or complicated screens but instead has colour-coded function controls that make range selection simple and speedy. Additionally, it can be operated ambidextrously with dual TEST and LOCK buttons at both sides.

The MFT1741+ is designed for tough environments, with IP54 protection against dust and water and an EN61010 CATIV safety rating. Indeed, the MFT can withstand accidental misuse and voltage transients, keeping you safe on the job.


* additional accessories required (sold separately)

More Information
ManufacturerMegger
Manufacturer Part Number1012-611
GTIN5036175240588
DatasheetDatasheet
Earth testYes
Type B RCD testYes
Write Your Own Review
You're reviewing:Megger MFT1741+ (Plus Version) Multifunction Tester
Your Rating

General Specification

Accuracy

Insulation test:

  • 1000 Volts 10 kΩ - 999 MΩ ±3% ±2 digits
  • 500 Volts. 10 kΩ - 500 MΩ ±3% ±2 digits >500 MΩ ±10% ±4 digits
  • 250 Volts. 10 kΩ - 250 MΩ ±3% ±2 digits >250 MΩ ±10% ±4 digits
  • 100 Volts. 10 kΩ - 100 MΩ ±3% ±2 digits >100 MΩ ±10% ±4 digits
  • EN61557 range: 10 kΩ - 999 MΩ (1000 V range)
  • Voltage display: ±3% ±3 digits ±0.5% of rated voltage
  • Max service error: ±15% ±2 digits.
  • Short circuit current: 1.5 mA nominal test current
  • Test current on load: ≥1 mA at min. pass values of insulation
  • Output voltage tolerance: -0% +20% at rated load or less
Continuity / Resistance:
  • Intrinsic accuracy: ±2% ±2 digits (0.01 Ω to 99.9 Ω), ±5% ±2 digits (100 Ω to 99.9 kΩ)
  • EN61557 range: 0.1 Ω to 99.9 kΩ
  • Open circuit voltage 5 V ±1 V
  • Test current at 200 mA (0 Ω to 2 Ω): >200 mA @ ≤2 Ω
  • Test current at 15 mA (0 Ω to 2 Ω): >15mA @ ≤2 Ω
  • Max Service error: ±12% ±2 digits.
Loop test 2Hi (L-PE, L-N, L-L):
  • Intrinsic accuracy: ±5% ±3 digits
  • Display range: 0.01 Ω to 1000 Ω
  • Supply: 48 V to 480 V* (45 Hz to 65 Hz)
  • Test current high: 4.0 A (at 230 V)
  • PSCC range: 20 kA
  • EN61557 range: 0.30 Ω to 1000 Ω
  • Max service error: ±10% ±2 digits
Loop test 3Lo, 2Lo (L-E):
  • Intrinsic accuracy: 0.01 Ω to 39.9 Ω ±5% ±5 digits
  • 40.0 Ω to 999 Ω ±10% ±5 digits
  • Display range: 0.01 Ω to 1000 Ω
  • Supply: 48 V to 280 V (45 Hz to 65 Hz)
  • Test current: Pulsed
  • PFC range: 20 kA
  • EN61557 range: 1.0 Ω to 1000 Ω
  • Max service error: ±10% ±2 digits
RCD test:
  • RCD type: AC, A, S, Type B (pure dc)
  • Intrinsic current accuracy:
  • No trip test: (1/2xI) –10% to 0%
  • Trip test: (1xI, 2xI and 5xI) +0% to +10%.
  • Ramp test current: ±5% ±1 digit
  • Trip time: ±1% ±1 ms
  • Programmable step increments: 10 mA to 50 mA - 1 mA steps, 50 mA to 500 mA - 5 mA steps, 500 mA to 1000 mA - 10 mA steps.
  • Supply: 48 V - 280 V 45 Hz to 65 Hz
  • Max service error: ±10% ±2 digits
Voltage:
  • Intrinsic accuracy: ±2% ±1 V
  • EN61557-1 Range: 10 V to 600 V
  • Phase rotation indication.
  • Max service error: ±5% ±2 digits
Frequency:
  • Intrinsic accuracy: ±0.5% ±2 digits
  • Resolution: 0.1 Hz
  • EN61557 Range: 15 Hz to 400 Hz
  • Max service error: ±5% ±3 digits
Earth Test Ranges:
  • Intrinsic accuracy: ±2.0% ±3 digits
  • ART method ±5.0% ±3 digits
  • Stakeless method ±7.0% ±3 digits
  • Resolution: 0.01 Ω
  • EN61557 range: 1.0 Ω to 1.99 kΩ
  • Current: 0.45 mA or 4.5 mA.
  • Noise rejection: 20 V pk/pk (7 V rms)
  • Max probe resistances: Rp, Rc = 100 kΩ @ 50 V
  • Max service error: ±20% ±3 digits
Current (via Clamp meter):
  • Intrinsic accuracy: ±5.0% ±3 digits
  • Resolution: 0.1 mA
  • EN61557 Range: 0.5 mA – 199 A
  • Max service error: ±10% ±2 digits
mV Sensor input
  • Including temperature (third party module)
  • ±1.0% ±2 digits
  • Range 0.0 mV to ±199.9 mV dc
  • Resolution 0.1 mV
Internal memory
  • Capacity 1000 results
  • Bluetooth® communication
Power consumption:
  • Nominal minimum: 60 mA (Voltage range with no input voltage)
  • Nominal maximum: 350 mA (Active Insulation test set to 1000 V / 1 MΩ)
  • Range: -20 °C to +55 °C
  • Temperature (via 3rd Party Module):
    • Intrinsic accuracy: ±1.0% ±2 digits
    • Resolution: 1 °C
    • Range: -20 °C to +100 °C
    Environmental Specification

    Temperature

    • Operational range: -10 °C to +55 °C
    • Storage range: -25 °C to +70 °C
    Humidity
    • Operating humidity: 90% R.H. at +40 °C max.
    Altitude
    • 2000 m to full safety specification.

    Weight: 1000 g ±10% including batteries but excluding test leads, accessories and carry case.

    Dimensions: 150 mm high x 85 mm wide x 235 mm deep (6 in. x 3.5 in. x 9.5 in.)

    IP rating: IP54

    Power Supply

    • Battery: Primary 6 x 1,5 V cells IEC LR6 type (AA alkaline,).
    • Battery: Rechargeable: 6 x 1.2 VNiMH cells EC HR6.
    • Display shows rechargeable [NiMH] when the battery type is changed in setup option (Section 10).

    Safety / EMC
    EMC In accordance with IEC61326 edition 2.
    Locations: Class B locations.
    Safety in accordance with BS EN 61010 -1 2010 + 61010 -30:2010
    Installation Category: 600 V CAT III / 300 V CAT IV. (Max Phase to Phase 550 V)
    In addition switch probe and test leads are designed to meet IEC 1010-031:2008, Double insulated to Installation Category III, 300 V phase to earth, 500 V phase to phase.

    • Megger MFT1741+ Multifunction Tester
    • Printed quick start guide
    • Full user guide on CD
    • Calibration certificate**
    • Switched probe SP5 (1002-774)
    • Neck strap - Megger embroidered (2001-509)
    • 3 Wire lead set with prods and clips (1001-991)
    • Mains plug test lead (BS1363) (6220-810)
    • AC battery charger (1002-736)
    • Large soft pouch with extra storage (1007-463)
      We found other products you might like!