Q: When using the Metrohm LLT 11 Live Line Tester, can you please explain why, when voltages are in phase the meter reads 2X phase to earth values = 12.7 kv, and when out of phase the meter reads phase to earth values 6.35kv?
A: The table on the front of the 11kV Tester details the In-Phase and Out of Phase Voltages expected on an 11kV System and on a 6.6kV System. From the Scale the In-Phase and Out of Phase Voltages can be easily measured.
To find the full explanation as to how this works, please read the following technical article on Phasing Calculation.
Q: Do you have the operating instructions for this product?
A: Yes, you can download a copy of the full instruction manual here.
Metrohm High Voltage Detectors (HVD Kits)
Q: What is the lowest voltage that can be detected with the HVD?
A: The minimum threshold for this model is 1.65kV, however the HVD range can be customised to your specific requirements.