Product Details
Fluke 1652B, Socket Tester, Voltage Tester & Part P Certificates.
You can also add a calibration checkbox to your order, choose from either the Transmille 2080 or the Seaward Powercheck 1557 (see "available options" above), and make even more savings when purchased as a kit.
The Fluke 1652B installation testers are feature packed to cater for the requirements of both domestic and commercial engineers. The large backlit display makes it easy to read the test results and all testers are supplied with fused test leads, remote switch probe, certificate of calibration, carry strap, quick start guide with full instruction manual on CD and a hard carry case.
The Fluke T120 voltage tester indicates live circuit voltage up to 690V with LED and LCD indication. In Addition the T120 can be used to show phase rotation and has audible contiunuity
The Fluke SM200 is a socket polarity tester with audible indication of correct wiring status
Where a tester is offered with a free manufacturers calibration certificate, this is issued at the time of manufacture and is valid from the date the equipment is commisioned into use. We offer an option of having the unit calibrated on the day of purchase for those who require it, and as such is charged at the rate shown.
Specfication
Supply Voltage Measurement
Voltage AC: 0V - 500V, 50/60 Hz, 0.1V Resolution
Mains Socket Test: L-PE or L-N Reverse
Insulation Test Ranges
Short Circuit Current: <2mA
250V: 0.01MΩ - 200MΩ
500V: 0.01MΩ - 500MΩ
1000V: 0.01MΩ - 1000MΩ
Accuracy: +/- 3%, +/- 3 digits up to 99MΩ
250, 500 & 1000V into 1mA
Output Voltage: +20% - 0% at rated load or less
Live Circuit Warnings
Insulation: User Selectable 25V or 50V threshold with visual warning
Continuity: >10V threshold
Audible Continuity
Ohms: 0.01Ω - 2000Ω (+/- 1.5%, +/- 3 digits)
Autoranging limits of 20Ω, 200Ω, 2000Ω
Test Current: >200mA @ 2Ω
Test Lead Null: Up To 2Ω (zero uses test button)
Loop Test Ranges
Line / Earth Single Phase 12A: 0.01Ω - 20Ω (Non Trip: +/- 3%, +/- 6 digits; High Current: +/- 2%, +/- 4 digits)
0.1Ω - 200Ω (Non Trip: +/-3%; High Current: +/-2%)
1Ω - 2000Ω (+/- 6%)
Phase to Phase 20A: 0.01Ω - 19.99Ω (+/- 3%, +/- 4 digits)
0.1Ω - 200Ω (+/- 2%)
1Ω - 2000Ω (+/- 6%)
Supply: 55V - 480V, 45Hz to 65Hz
Supply: 55V - 270V, 45Hz to 65Hz
Prospective Shortcircuit Current PSC
Prospective fault current = nominal voltage / loop resistance
Range: 0 - 10kA or 0 - 50 kA
RCD Ranges
Supply: 100V - 265V, 45Hz to 65Hz
Ranges: 1000mA, 500mA, 300mA, 100mA, 30mA, 10mA
Type: 1/2I, I, 5I
Ramp Test
Current Accuracy:
No Trip (1/2I): 0% to -10% of test current
Trip (I and 5I): +10% to 0%
Trip Time Accuracy: +/- 1%, +/- 1ms
Selection: 25V or 50V
Power Supply
6 x 1.5 Alkaline Cells Type LR6
Battery Life: 3000 continuity tests