All electrical appliances using mains voltage have to provide at least 2 levels of protection to the user. This is to ensure that if one of the protection methods were to fail, there is the back-up of the second method still in place. This makes electrical equipment very safe to use.

This article is an extract from Martindale Portable Appliance Testing – an illustrated guide. The book looks at what the current requirements are, how to identify appliance types, tests that need to be carried out and how to maintain accurate records, as well as examples of common appliances and how they should be tested. Whether you are new to PAT Testing or need to get up to date with the Code of Practice 4th Edition, we highly recommend having a copy of the Martindale Portable Appliance Testing – an illustrated guide handy at all times.

Depending on how exactly the protection is provided, electrical appliances are put into 5 Classes of equipment construction which are Class I, II, III, 0 and 01. Of these the most important are Class I & II.

1

For completeness, all the Classes are described below:
CLASS I

Here the protection is provided by a combination of insulation and use of the mains Earth. It is best shown by referring to the photograph of an electric heater that has been taken apart (Fig 4.1).

Inside the fire, the brown LIVE wire and the blue NEUTRAL wire connect to a plastic connector. The green/yellow EARTH wire connects to the metal case of the fire. The user is protected from electric shock by the plastic insulation of the cables. This holds the LIVE and NEUTRAL wires in place and prevents them from touching the metal case of this electric heater.

This plastic insulation of the cables is known as basic insulation. If this basic insulation were to fail, say due to abrasion from excessive movement of the cable where it touches the metal case, then the user of the fire could receive an electric shock if not for the fact that the EARTH wire is present.

By connecting to the metal case of the electric heater, the EARTH wire keeps all this metal at EARTH potential. What this means is that it is impossible to get an electric shock even when the metal case of the fire is connected directly to the LIVE voltage. In practice a fuse would blow either in the plug or the main fuse box to protect the user or a RCD would trip.

In summary, in Class I appliances the user is protected by a combination of basic insulation and the provision of an EARTH connection, thus providing two levels of protection.

2

CLASS II

In a Class II appliance, the user is protected by at least two layers of insulation. For this reason, Class II appliances are also known as Double Insulated. They do not require an Earth connection. This is a Class II electric drill which has been opened up (Fig 4.3). Inside, as well as the plastic connector providing basic insulation, there is additional insulation provided by the plastic enclosure of the drill. Class II appliances are always identified by the double box symbol on the rating plate (Fig 4.4).

3

CLASS III

Equipment built to the Class III standard is designed to be supplied from a special safety isolating transformer whose output is known as Separated Extra-Low Voltage or SELV. This must not exceed 50 V AC and is normally below 24V or 12V. All Class III appliances are marked as shown here (Fig 4.5). There is no use of an Earth in Class III appliances. The electrical safety of Class III appliances is taken care of in the safety isolating transformer design where the separation between the windings is equivalent to double insulation. The transformer is marked as shown here (Fig 4.5).

4

CLASS 0 & 01

This type of equipment is not for normal use in business or residential environments. It is just presented here for completeness. Class 0 appliances depend only on basic insulation for protection from electric shock. For this reason, they do not have 2 levels of protection built in and are not allowed for sale. The brass lamp shown here (Fig 4.6) is an example of a two wire, metal cased appliance with only basic insulation. There is no provision for connection of an Earth to the bulb holder.

5

In Class 01 appliances, there is provision for an Earth connection, but it is wired with either twin core cable or only has a 2-pin plug, so an Earth cannot be connected. As in Class 0 equipment, one is dependent only on basic insulation for protection from electric shock. As they only have 1 level of protection, Class 01 appliances are not
allowed for sale.
Identifying Class I & Class II Appliance

As the tests carried out on Class I and Class II appliances differ, it is important to identify one from the other. There is no other area of PAT Testing that causes more confusion than this and there are many myths surrounding this. Here is a list of some of them:

  • If there is a fuse in the plug, then it must be Class I;
  • It is made of metal so it must be Class I;
  • The case is plastic so it must be Class II;
  • It has a three core cable so it must be Class I;
  • The plug has a metal Earth pin so it must be Class I.

None of the above statements is a fool-proof way to identify Class I and Class II appliances and some are quite misleading. The easiest rule to apply is the one below:

6

 

Example – Kettle

The rating plate on this kettle (Fig 4.7) clearly has no “double-box” symbol, so using our rule, it must be Class I. The Earth connection from the plug is terminated on the outside metal casing of the heating element.

7

 

Example – Plug-top power supply

The rating plate on this Plug-top transformer (Fig 4.8) clearly shows the symbol, so this is a Class II appliance. (Note that it has a plastic Earth pin, as an Earth is not required for Class II) (Not all Class II appliances have a plastic Earth pin).

8

Example – Mains extension

The rating plate on this extension is moulded in the plastic (Fig 4.9). It clearly does not have a symbol, so it must be a Class I. (Note that this is an example of a Class I appliance that is in a plastic case).

9

 

Example – Table lamp

The rating plate on this table lamp (Fig 4.10) clearly shows the symbol so it is a Class II appliance. (Note that this is a Class II appliance that is largely in a metal enclosure). The bulb holder is made of plastic and provides the required double insulation.

10

 

Example – Desk fan

The rating plate for this fan (Fig 4.11) not only does not have a symbol, it also says that the appliance must be earthed. So this is clearly a Class I appliance. (Note that it does not have any user accessible metal parts (see page 45).

11

 

Example – Metal Lamp

If this metal lamp had a rating plate, then it would be a Class I appliance as it has an Earth point on the lamp holder (Fig 4.12). However, as the rating plate is missing, this should be investigated to establish if it is Class I or less likely Class II. If it is old, it may be Class 0 and should not be used.

12

A practical decision may need to be made in some environments (eg schools) where rating labels are often removed. Knowledge of the class of other items of the same model may be applied.
Are Class I and Class II appliances just as safe?

As both have 2 levels of protection built in, they are both safe for general use. However with a Class I appliance, one of the means of safety is provided by the Earth connection. For this to be effective, the wiring in the building has to be inspected regularly to check that the Earth in the mains socket is correctly taken to the local Earth potential. This is usually taken from the Earth sheathing of the mains cable coming into the premises, or by driving a local stake into the ground. So Class I appliances depend on the external wiring in the building to fully provide the 2 levels of protection.

Class II appliances however, always provide 2 levels of protection irrespective of the status of the wiring installation. Both layers of protection are built into the design making Class II appliances safer than Class I appliances.

This article is an extract from Martindale Portable Appliance Testing – an illustrated guide. The book looks at what the current requirements are, how to identify appliance types, tests that need to be carried out and how to maintain accurate records, as well as examples of common appliances and how they should be tested. Whether you are new to PAT Testing or need to get up to date with the Code of Practice 4th Edition, we highly recommend having a copy of the Martindale Portable Appliance Testing – an illustrated guide handy at all times.
Things to remember about Class I and Class II:

  • If the rating plate has a double box then it is Class II;
  • If the rating plate does not have a double box then assume Class I;
  • Class II appliances are double insulated and inherently safer than Class I appliances;
  • Class I appliances depend on the Earth provided by the installation wiring for their safety.